Experimental Study of Heat Pipe Heat Exchanger in Hospital HVAC System for Energy Conservation

Putra, Nandy Setiadi Djaya and Anggoro, Trisno and Winarta, Adi (2017) Experimental Study of Heat Pipe Heat Exchanger in Hospital HVAC System for Energy Conservation. International Journal on Advanced Science Engineering Information Technology, 7 (3). pp. 871-877. ISSN 2088-5334

[img] Text (Similarity Check Document)
Experimental Study of Heat Pipe Heat Exchanger in Hospital HVAC System for Energy Conservation.pdf

Download (2MB)
[img] Text (correspondence document)
korespodensi_Ijaseit_final.pdf

Download (1MB)
Official URL: http://ijaseit.insightsociety.org/index.php?option...

Abstract

The hospitals Heating, Ventilation and Air Conditioning (HVAC) systems consume large amounts of energy due to the specific requirements that must be met to ensure environmental conditions are healthy, convenient, and safe. Therefore, to reduce electricity consumption without sacrificing comfort and improving indoor air quality, the utilizing of heat pipe heat exchanger (HPHE) is necessary and highly recommended. An experimental study was conducted to investigate the thermal performance of heat pipe in recovering the heat of an exhaust air from a room simulator. HPHE consists of several tubular heat pipes with water as a working fluid and staggered by up to six rows. The outer diameter of each heat pipe is 13 mm and length of 700 mm with fins mounted on each heat pipe. A series of experiments was conducted to determine the effect of inlet air temperature. The influence of the number of heat pipe rows and air velocity was also investigated. The experiments show that the higher inlet air temperature, the more effective the HPHE performance has become. The cooling capacity of the system has increased. It was indicated by the decrease of air temperature entering the evaporator by 2.4 °C with the effectiveness of 0.15. This result was achieved when using six rows HPHE, air velocity 1 m/s, and evaporator inlet air temperature 45 °C. When air velocity was double to 2 m/s, the system reaches the largest amount of heat recovered of 1404.29 kJ/hour. The overall use of energy in HVAC system from the annual prediction of heat recovery for 8 h/day and 365 days/year will decrease significantly 0.6-4.1 GJ/yr.

Item Type: Article
Subjects: Ilmu Teknik > Ilmu Keteknikan Industri > Teknik Mesin (dan Ilmu Permesinan Lain)
Ilmu Teknik > Ilmu Keteknikan Industri > Teknik Refrigerasi
Divisions: Jurusan Teknik Mesin > Prodi D4 Teknologi Rekayasa Utilitas > Publikasi
Depositing User: Adi Winarta
Date Deposited: 08 May 2023 11:23
Last Modified: 10 May 2023 02:53
URI: http://repository.pnb.ac.id/id/eprint/5686

Actions (login required)

View Item View Item