Suamir, I Nyoman and Baliarta, I Nyoman Gede and Arsana, Made Ery and Sudirman, Sudirman and Sugina, I Made (2020) Field-based Analyses on Approach Temperatures for Performance Evaluation of Centralized Air Conditioning System in a Shopping Mall Building. In: International Conference on Science and Technology 2019, 17-18 Oktober 2019, Surabaya.
Text (Article)
Paper_29_PI_INSuamir_2020.pdf - Published Version Available under License Creative Commons Attribution Non-commercial Share Alike. Download (838kB) |
|
Text (Similarity Check)
Originality Report - Paper_29_PI_INSuamir_2020.pdf - Supplemental Material Available under License Creative Commons Attribution Non-commercial Share Alike. Download (309kB) |
|
Text (Correspondence / Review)
Paper_29_PI_INSuamir_2020_Review.pdf - Supplemental Material Available under License Creative Commons Attribution Non-commercial Share Alike. Download (219kB) |
Abstract
This paper presents field analyses on the influences of condenser and evaporator approach temperatures of water cooled air conditioning system for a shopping mall. The mall building comprises food and non-food retail stores and uses a centralized air conditioning (AC) system to condition the entire building. The AC system comprises three chillers with the same cooling capacity. Chillers' performance parameters included power consumption, condensing and evaporating temperatures, evaporator-condenser approach temperatures, pressure drop and cooling capacity parameters were hourly recorded for a period of one year. Performance characteristics of each chiller were evaluated at different condenser and evaporator approach temperatures and regression analyses were also established to examine the correlations and influences of the approach temperatures on the chillers' performance. The analyses results showed that the increase of condenser approach temperature could increase the power consumption and reduce the coefficient of performance (COP) of the chillers. While evaporator approach temperature was found to have insignificant effect to the chiller performance. The results also showed that for the investigated chillers with condenser and evaporator approach temperatures maintained below 2 K, the approach temperatures had negligible correlation to the power consumption and the overall performance of the chillers. At this operational conditions, the water cooled air conditioning systems could operate at their best possible performance.
Item Type: | Conference or Workshop Item (Paper) |
---|---|
Subjects: | Ilmu Teknik > Ilmu Keteknikan Industri > Teknik Mesin (dan Ilmu Permesinan Lain) Ilmu Teknik > Ilmu Keteknikan Industri > Teknik Refrigerasi |
Divisions: | Jurusan Teknik Mesin > Prodi D4 Teknologi Rekayasa Utilitas > Publikasi |
Depositing User: | I Nyoman Suamir |